Machine Status and Basic Operations
Q: What does âMACHINE NOT READY TO STARTâ status mean?
A: This status appears when:
- The machine has not completed the âDILUTIONâ cycle before power off
- Thereâs a critical trip condition (TOTAL SHUTDOWN)
- The machine is in compulsory dilution after certain alarms
- Field interlocks are not satisfied (pumps, flow switches, etc.)
Resolution Steps:
- Check if dilution cycle needs to be completed (wait 20 minutes)
- Verify all field interlocks are healthy
- Reset any active alarms after addressing root cause
- Ensure Heat Source Water and District Water pumps are running
Q: Why wonât my heat pump start?
A: Common reasons for startup failure:
- Heat Source Water Flow Switch not activated
- Heat Source Water DP Switch not activated
- Heat Source Water Pump feedback signal missing
- Machine in TRIP or DILUTION status
- Critical alarms present
Troubleshooting Steps:
- Check Heat Source Water flow rate (should be 50-60% of rated minimum)
- Verify Heat Source Water pump is running and feedback signal received
- Check for any active alarms on operator panel
- Ensure machine status shows âREADY TO STARTâ
- Wait for startup sequence timeout (10 minutes) if flow issues persist
Q: What is the DILUTION cycle and why does it occur?
A: DILUTION is a 20-minute safety cycle that:
- Prevents LiBr crystallization in heat exchangers
- Equalizes concentration and temperature throughout the system
- Occurs automatically after certain trips or power failures
- Cannot be interrupted when marked as âCOMPULSORY DILUTIONâ
When DILUTION occurs:
- After power failure (>3 minutes requires compulsory dilution)
- Generator temperature high trips
- Refrigerant pump trips
- Normal machine shutdown
- Various temperature sensor errors
TOTAL SHUTDOWN Alarms
Q: What should I do when I get âANTIFREEZE TRIPâ alarm?
A: This critical alarm occurs when Heat Source Water outlet temperature drops below freezing point.
Immediate Actions:
- Machine automatically stops all pumps and closes steam valve
- Heat Source Water pump continues running to prevent freezing
- DO NOT restart until temperature rises above setpoint + hysteresis
Root Cause Investigation:
- Check Heat Source Water supply temperature
- Verify adequate flow rate through evaporator
- Inspect for blockages in Heat Source Water circuit
- Check if load demand is too low causing overcooling
Q: How do I handle âHEAT SOURCE WATER PUMP TRIPâ alarm?
A: This alarm indicates the Heat Source Water pump is not responding or has tripped.
Troubleshooting Steps:
- Check Heat Source Water pump motor starter
- Verify electrical connections to pump
- Ensure pump feedback contact is wired correctly
- Check for mechanical issues with pump
- Reset pump motor protection if tripped
- Alarm can only be reset after pump run feedback is received
Q: What causes âHEAT SOURCE WATER FLOW SWITCH TRIPâ?
A: Flow rate has dropped below 50-60% of rated value.
Resolution:
- Check Heat Source Water pump operation
- Inspect for blockages in piping
- Verify flow switch setting (should be 50-60% of rated flow)
- Check for closed valves in Heat Source Water circuit
- Look for air locks in system
- Ensure adequate water supply pressure
Q: âABSORBENT PUMP TRIPâ â what should I check?
A: The absorbent pump motor has drawn excessive current or AC drive has faulted.
Diagnostic Steps:
- Check MPCB/Overload relay status â reset if tripped
- Verify AC drive status and error codes
- Check for mechanical binding in pump
- Inspect electrical connections
- Verify pump is not running dry
- Check LiBr solution levels in system
DILUTION Alarms
Q: Why do I get âGENERATOR TEMPERATURE HIGHâ alarm?
A: Generator temperature exceeded safe operating limit, risking LiBr crystallization.
Causes and Solutions:
- Excessive steam flow: Check steam control valve operation and setpoints
- Low District Water flow: Verify District Water pump and flow rates
- High District Water inlet temperature: Check cooling system
- Faulty temperature sensor: Calibrate or replace sensor
- PID control issues: Review controller parameters
Prevention: Monitor generator temperature trends and adjust steam flow accordingly
Q: What does âDISTRICT HOT WATER INLET TEMP LOWâ mean?
A: District Water inlet temperature dropped below minimum setpoint, risking LiBr crystallization in absorber.
Resolution:
- Check District Water supply temperature
- Verify heating system upstream is functioning
- During startup, this safety is bypassed for first 30 minutes
- Adjust setpoint if consistently triggering during normal operation
- Ensure adequate heat rejection capacity
Q: âREFRIGERANT PUMP TRIPâ â how do I resolve this?
A: Refrigerant pump motor overcurrent or mechanical failure.
Troubleshooting:
- Reset MPCB/Overload relay
- Check refrigerant level in evaporator
- Verify pump not cavitating (check suction pressure)
- Inspect pump mechanical condition
- Check electrical supply to pump
- Ensure refrigerant level electrodes are functioning
Level Control Issues
Q: How do the level electrodes work?
A: Three sets of level electrodes monitor solution levels:
Absorber Level (AE1-AE4):
- AE1: 50% sight glass level
- AE2: 25% sight glass level
- AE3: 0% sight glass level (critical low)
- AE4: Reference electrode
Actions:
- Below AE2: Auto blowdown valve opens
- Below AE3: Steam valve closes completely
- Above AE1: Auto blowdown valve closes
Generator Level (GE1-GE3):
- GE1: Normal maximum level
- GE2: Restart level
- GE3: Reference electrode
Q: âAuto blowdown valve not workingâ â what to check?
A: Auto blowdown valve transfers refrigerant to absorber when level is low.
Troubleshooting:
- Verify absorber level electrode signals
- Check valve electrical connections
- Ensure refrigerant pump is running (valve only opens when pump ON)
- Inspect valve for mechanical binding
- Verify valve solenoid coil integrity
- Check PLC logic and I/O modules
Crystallization Prevention
Q: How does the system prevent LiBr crystallization?
A: Multiple protection methods:
Steam Control Valve Modulation:
- PLC calculates solution concentration and crystallization temperature
- Maintains safe temperature margin above crystallization point
- Overrides capacity control when crystallization risk detected
Absorber Level Control:
- Low level indicates possible crystallization in spray lines
- Auto blowdown dilutes solution when level drops
Temperature Monitoring:
- Multiple temperature sensors monitor critical points
- Automatic valve closure when safe limits exceeded
Q: What if I suspect crystallization has occurred?
A: Signs of crystallization:
- Rapidly dropping absorber level
- High generator temperature with low steam flow
- Poor heat transfer performance
- Frequent level-related trips
Recovery Actions:
- Allow extended dilution cycle (may take several cycles)
- Check all solution temperatures
- Verify proper operation of all level electrodes
- Monitor concentration calculations on HMI
- Contact service technician if problem persists
Control System Issues
Q: Steam control valve not responding properly?
A: Control valve issues affect capacity and safety.
Diagnostics:
- Check valve position feedback vs. command signal
- Verify 4-20mA control signal integrity
- Test valve manually from HMI (Service Menu)
- Check PID controller parameters
- Inspect valve actuator and positioner
- Verify steam supply pressure and valve sizing
Control Modes:
- Slow opening (thermal shock prevention)
- District Water temperature PID control
- Generator temperature limiting
- Crystallization prevention override
- Absorber level control override
Q: PLC communication errors â how to diagnose?
A: Communication between PLC and components:
HMI Communication:
- Check Ethernet cable connections
- Verify IP address settings
- Check for electromagnetic interference
- Restart HMI if screen frozen
- Verify PLC CPU status LEDs
I/O Module Issues:
- Check module LED status indicators
- Verify field wiring connections
- Check 24VDC supply to modules
- Replace suspect modules
- Verify module configuration in PLC program
Sensor and Measurement Issues
Q: Temperature sensor error alarms?
A: Temperature sensor failures affect control and safety:
Critical Sensors (cause TOTAL SHUTDOWN):
- Heat Source Water Outlet Temperature
- Antifreeze Thermostat
Dilution-causing Sensors:
- District Hot Water Inlet/Outlet Temperature
- Generator Temperature
- U-tube Temperature
- Spray Solution Temperature
Warning-only Sensors:
- Heat Source Water Inlet Temperature
- Dilute Solution Temperature
- Generator Top/Bottom Temperature
- Heat Reclaimer Outlet Temperature
Troubleshooting:
- Check sensor wiring and connections
- Verify RTD continuity (typically 100Ω at 0°C)
- Check for moisture in junction boxes
- Verify proper sensor mounting
- Replace faulty sensors with identical specifications
Q: Vacuum transmitter reading incorrectly?
A: Vacuum measurement affects purging operation:
Checks:
- Verify 4-20mA signal at PLC input
- Check transmitter calibration
- Inspect sensing lines for blockages
- Ensure proper electrical connections
- Compare with manual vacuum gauge if available
Automatic Purging System
Q: âPURGE PUMP NOT DEVELOPING VACUUMâ alarm?
A: Purge pump cannot achieve ultimate vacuum setpoint.
Troubleshooting:
- Check purge pump motor operation
- Inspect pump mechanical condition
- Verify all manual valves are properly positioned
- Check for air leaks in vacuum lines
- Clean or replace pump oil if applicable
- Verify ultimate vacuum setpoint (typically 2-5 mmHg)
Q: âTANK PURGING FREQUENCY HIGHâ warning?
A: More than 2 automatic purges per day indicates possible air leakage.
Investigation:
- Check machine shell for air leaks
- Inspect all gaskets and seals
- Verify proper torque on flanged connections
- Check purge system valves for proper sealing
- Monitor vacuum levels during operation
- Consider leak detection testing
Q: Purging system stuck in manual mode?
A: System shifted to manual due to malfunction.
Resolution:
- Address root cause that triggered manual mode
- Verify purge pump develops ultimate vacuum
- Test all solenoid valves manually
- Check vacuum transmitter operation
- Reset to AUTO mode only after confirming proper operation
Preventive Maintenance Reminders
Q: What are key maintenance items to prevent trips?
A: Regular maintenance prevents most alarm conditions:
Daily Checks:
- Verify all pumps running smoothly
- Monitor temperature and pressure readings
- Check for unusual noises or vibrations
- Verify adequate solution levels
Weekly Checks:
- Clean HMI screen and check for alarms
- Verify flow switch and pressure switch operation
- Check electrical connections for tightness
- Monitor purging frequency and effectiveness
Monthly Checks:
- Calibrate temperature sensors
- Test safety shutdown systems
- Verify control valve operation
- Check solution concentration
- Inspect electrical panels for dust/moisture
Annual Checks:
- Complete control system calibration
- Replace batteries in transmitters
- Comprehensive leak testing
- Update PLC/HMI software if needed
- Professional controls system inspection
Emergency Procedures
Q: What to do in case of power failure?
A: Power failure during operation triggers automatic protection:
Automatic Actions:
- Machine enters DILUTION on power restoration
- If power loss <3 minutes: dilution can be bypassed
- If power loss >3 minutes: compulsory dilution required
Manual Actions:
- Do not attempt to restart immediately
- Allow dilution cycle to complete
- Check for any damage during power outage
- Verify all systems normal before restart
- Monitor closely during first few hours of operation
Q: Emergency shutdown procedure?
A: If immediate shutdown required:
Steps:
- Press STOP button on HMI
- If HMI unresponsive, use emergency stop button
- Close steam supply valve manually if necessary
- Ensure Heat Source Water pump continues running
- Do not stop District Water pump immediately
- Allow system to cool gradually
- Log all actions taken and conditions observed
Advanced Diagnostics
Q: How to interpret trend data for troubleshooting?
A: Use data logging for pattern analysis:
Key Parameters to Monitor:
- Generator and District Water temperatures
- Steam valve position over time
- Pump runtime hours and trip frequency
- Concentration calculations
- Vacuum levels and purging patterns
Trending Analysis:
- Gradual temperature increases may indicate fouling
- Frequent valve adjustments suggest control issues
- Increasing purge frequency indicates air leakage
- Pump trip patterns may show mechanical wear
Q: System performance declining â what to check?
A: Performance degradation troubleshooting:
Heat Transfer Issues:
- Check for fouling in heat exchangers
- Verify proper solution concentration
- Monitor approach temperatures
- Check for air in solution circuits
Control System Issues:
- Verify sensor calibration accuracy
- Check PID control parameters
- Monitor valve response times
- Verify proper setpoint values
Mechanical Issues:
- Check pump performance curves
- Monitor vibration levels
- Verify proper solution levels
- Check for internal leakage
Frequently Asked Questions (FAQs)
Q: Why does my heat pump show âMACHINE NOT READY TO STARTâ?
A: Check if dilution cycle completed, resolve critical alarms, verify field interlocks (pumps, flow switches), and ensure Heat Source Water pump is running.
Q: Why wonât my heat pump start?
A: Check Heat Source Water flow switch, differential pressure, pump feedback, or active alarms. Ensure âREADY TO STARTâ status and wait 10 minutes if flow issues persist.
Q: What is the DILUTION cycle?
A: A 20-minute safety cycle prevents LiBr crystallization, equalizes concentration, and runs after trips, power failures (>3 min), or shutdowns. Itâs compulsory for some alarms.
Q: How to handle âANTIFREEZE TRIPâ alarm?
A: Heat Source Water temp below freezing triggers shutdown. Keep pump running, check supply temp, flow rate, or low load. Donât restart until temp rises.
Q: What causes âHEAT SOURCE WATER PUMP TRIPâ?
A: Check pump motor starter, electrical connections, feedback signal, or mechanical issues. Reset motor protection after fixing.
Q: Why does âHEAT SOURCE WATER FLOW SWITCH TRIPâ occur?
A: Flow below 50-60% rated value. Check pump, piping blockages, flow switch settings, or closed valves.
Q: How to fix âABSORBENT PUMP TRIPâ?
A: Check MPCB/overload relay, AC drive errors, mechanical binding, or LiBr levels. Reset after resolving issues.
Q: Why do I get âGENERATOR TEMPERATURE HIGHâ alarm?
A: Caused by excessive steam, low District Water flow, high inlet temp, or sensor issues. Check valve, flow, and PID settings.
Q: What does âDISTRICT HOT WATER INLET TEMP LOWâ mean?
A: Inlet temp too low risks crystallization. Check supply temp, heating system, or adjust setpoint. Bypassed for 30 min at startup.
Q: How to resolve âREFRIGERANT PUMP TRIPâ?
A: Check MPCB/overload, refrigerant level, pump cavitation, or mechanical issues. Reset after fixing.
Q: How do level electrodes work?
A: Absorber electrodes (AE1-AE4) monitor levels: AE1 (50%), AE2 (25%), AE3 (0%). Below AE2 opens blowdown; below AE3 closes hot water/steam valve.
Q: Auto blowdown valve not working. What to check?
A: Verify electrode signals, valve connections, solenoid, or PLC logic. Ensure refrigerant pump is on.
Q: How does crystallization prevention work?
A: Modulates steam valve based on concentration, maintains safe temp margin, and uses blowdown for low absorber levels. Monitor sensors for limits.
Q: What if crystallization occurs?
A: Signs: low absorber level, high generator temp, poor performance. Run extended dilution, check temps and electrodes, or contact us.
Q: Steam control valve not responding. How to diagnose?
A: Check feedback vs. 4-20mA signal, test manually, verify PID, actuator, or steam pressure.
Q: PLC communication errors. How to fix?
A: Check Ethernet cables, IP settings, module LEDs, 24VDC supply, or replace faulty modules.
Q: Temperature sensor error alarms?
A: Critical sensors (Heat Source Water Outlet, Antifreeze) cause shutdown; others trigger dilution or warnings. Check wiring, RTD continuity, or replace sensors.
Q: Vacuum transmitter reading incorrectly?
A: Verify 4-20mA signal, calibration, sensing lines, or compare with manual gauge.
Q: Why âPURGE PUMP NOT DEVELOPING VACUUMâ alarm?
A: Check pump motor, mechanical condition, valve positions, air leaks, or oil. Verify setpoint (2-5 mmHg).
Q: What does âTANK PURGING FREQUENCY HIGHâ mean?
A: Over 2 purges/day suggests air leaks. Inspect shell, gaskets, valves, and monitor vacuum trends.
Q: Purging stuck in manual mode. How to fix?
A: Resolve trigger cause, verify pump vacuum, test solenoid valves, and reset to AUTO mode.
Q: Key maintenance to prevent trips?
A: Daily: check pumps, temps, alarms. Weekly: verify flow switches, connections. Monthly: calibrate sensors, test alarms. Annually: full calibration, leak tests.
Q: What to do during power failure?
A: Wait for dilution on power restoration. If <3 min, bypass possible; if >3 min, compulsory dilution. Check systems before restart.
Q: Emergency shutdown procedure?
A: Press STOP on HMI, use emergency stop if needed, close steam valve, keep pumps running, and allow gradual cooling.
Q: How to interpret trend data?
A: Monitor generator/District Water temps, valve position, pump trips, concentration, and vacuum. Gradual changes suggest fouling; frequent purges indicate leaks.
Q: System performance declining. What to check?
A: Check fouling, solution concentration, sensor calibration, PID settings, pump performance, or leaks. Use trend data for analysis.